초록

The objectives of this paper are to provide information on the characteristics of the discharge signals in a low-voltage indoor outlet. Most of electrical fires are caused by short circuits, overheating of wires, deterioration and incomplete connection of wiring devices. The last two cases are predictable before the occurrence of fire because of its slow progress. We have simulated the discharge signals caused by the deterioration and incomplete connection of wiring devices using aged outlets. From the experimental data, we could characterize the frequency spectrums of the discharge signals depending on the cases. The higher frequency components of the signal are attenuated by the capacitance and inductance of power lines as the measuring point is getting away from the discharges. Main frequency components of the discharge signal are existent at 600kHz - 1.5MHz in incomplete connections and at 210H7z - 8MHz in deteriorations of the outlet.

키워드

참고문헌

  1. 화재통계연보, 행정자치부, pp. 87-90, 2003
  2. 전기재해 통계분석, 한국전기안전공사, pp. 3-20, 2003
  3. 월간전기 편집부, 전기사고별 원인분석과 방지대책, 전우문화사, pp. 231-280, 1995
  4. Chunlin Li, Francis Dawson, Hassan Kojori, Chris Meyers and Edwin Yue, 'Arc Fault Detection and Protection-Opportunities and Challenges', SAE Technical Papers, 2003-01-3037, 2003
  5. Neiger et al., 'Arc Fault Detector With Circuit Interrupter and Early Arc Fault Detection', US Patent no. 6, 407, 893, 2002
  6. James M. McCormick, Pete Theisen, 'Arc Fault Circuit Interrupter Development Overviews', SAE Technical Papers, 2003-01-3233, 2003
  7. 김희동, '운전중 대형 터빈발전기에서 절연상태 평가', 대한전기학회 논문지, 제53권, 6호, pp. 324-329, 2004
  8. 김정태, 이호근, 임윤석, 김지홍, 구자윤, 'SOM 알고리즘을 이용한 부분방전 패턴인식에 대한 연구', 대한전기학회 논문지, 제53권, 10호, pp. 515-522, 2004
  9. 안상필, '전기적 아크특성을 고려한 아크사고차단기 성능평가 및 국내도입방안',pp.84-89, 월간 전기기술, 2004. 4
  10. KS C 0903, 소형전기기기의 기계적 충격시험방법, 한국표준협회, 2002. 11