UHF Narrow Band Type Partial Discharge Diagnosis Method for the Internal Insulation Performance Verification of the Gas Insulated Switchgear

가스절연 개폐장치의 내부절연 성능검증을 위한 UHF 협대역 부분방전 진단법

  • Published : 2005.09.01

Abstract

A method for partial discharge diagnosis based on UHF narrow band type for GIS has been developed and calibrated. In generally, PD cannot be directly measured under on-line condition, but we can indirectly measure the electromagnetic wave made by PD using the high-frequency antenna. Compared with VHF band, electromagnetic waves of UHF band have a low influence for external noise in high-voltage substation. Therefore, we can detect the real abnormality with several pC in GIS using UHF narrow-band type method. For the case of no internal VHF sensor for GIS of the domestic substation, it has applied to use the external UHF sensor attached in spacer in GIS of existing substation. In this paper, we firstly described the technique of partial discharge measurement using frequency analysis and phase analysis in UHF band. Secondly, we presented the results of sensitivity test, the relationship of dBm-pC and diagnosis result of the cause of PD source by phase analysis. And then, we report the diagnosis result of partial discharge on the real GIS in domestic substation. These results make above method applicable for measurement of quantity and cause of PD for real operation GIS in high-voltage substation.

Keywords

References

  1. J.B.Kim, M.S.Kim, K.S.Park, W.P.Song, D.S.Kim, 'Development of Monitoring and Diagnostic System for SF6 Gas Insulated Switchgear', IEEE Conference record of the 2002 IEEE International symposium on Electrical Insulation, April 7-10, 2002, 453-456 https://doi.org/10.1109/ELINSL.2002.995972
  2. 김정배, 김민수, 송원표, 김덕수, 전찬석, 길경석, '가스절연개폐장치용 감시시스템 적용에 관한 연구', 대한전기학회 논문지, Vol.51C, No.1, Jan 2002
  3. 이동철, '초고압 GCB/GIS 성능 및 품질 향상 대책', 전력용 개폐장치 연구회 제1차 기술발표회 및 토론회 자료,2000.07, p.5-10
  4. M.D.Judd, O.Farish, B.F.Hampton, 'The Excitation of UHF Signals by Partial Discharges in GIS', IEEE Trans. dielectrics and Electrical Insulation, Vol. 3, No. 2, April 1996 https://doi.org/10.1109/94.486773
  5. R. Kurrer, K. Feser, 'The Application of Ultra-High-Frequency Partial Discharge Measurements to Gas-Insulated Substations', IEEE Tras. on Power Delivery, Vol.13, No.3, July 1998 https://doi.org/10.1109/61.686974
  6. Fumihiro Endo, 'Risk Assessment of Defects in GIS by PD Diagnostics', CIGRE WG15-03 TF15.03.09 Munchen Meeting, March, 2000
  7. M.runde, T.Aurud L.E., Lundgaard, G.E.Ottesen, K.Faugstad, 'Acoustic Diagnosis of High Voltage Circuit-Breakers', IEEE Trans. on Power Deliver, Vol.7, No.3, July 1992 https://doi.org/10.1109/61.141847
  8. C.Neumann, B.Krampe, R.Feger, K.Feser, M.Knapp, A.Breuer, V.Rees, 'PD Measurements on GIS of different designs by non-conventional UHF Sensors', CIGRE 2000, 15-305
  9. 김정배, 정재룡, 김민수, 송원표, 김맹현, 고희석, 최인혁, 'UHF 부분방전 진단법에 의한 가스절연 개폐장치의 성능검증', 2004년도 대한전기학회 전기설비전문위원회 춘계학술대회, 2004.05. p.132-135
  10. CIGRE TF15/33.03.05, 'Partial Discharge Detection System for GIS : Sensitivity Verification for The UHF Method and The Acoustic Method', ELECTRA, No.183, April 1999
  11. 김정배, 정재룡, 김민수, 송원표, 김맹현, 고희석, 최인혁, '초고압 GIS용 부분방전 UHF 센서의 현장성능시험 연구', 2004년도 대한전기학회 전기설비전문위원회 춘계학술대회, 2004.05, p.121-122