Empirical Modeling on the Breaking Characteristics of Power Current Limited Fuse

전력용 백업퓨우즈 차단특성 모델링

  • Published : 2005.09.01

Abstract

In this paper the modeling of interrupting characteristics of a high voltage current limiting fuse to be used in a power distribution system is introduced. In order to reduce the level of energy which can be absorbed by equipment during fault current flow, a high voltage current limiting fuse can generate a high voltage at the fuse terminals. Consequently it is necessary to model and analyze precisely the voltage and current variation during a CL fuse action. The characteristics of CL fuse operation modeled by electrical components have been performed with less than 6 [$\%$] errors. So the fuse designer or manufacturer can estimate the characteristics of CL fuse operation by using this modeling. The Electro Magnetic Transient Program (EMTP) is used to develop the modeling.

Keywords

References

  1. Sei-Hyun Lee, Sang-Ok Han, 'The Effects of Design Parameter to Interrupt Optimally for High Voltage CL Fuse', KIEE, Vol. 48-3, pp.185-191, 1999
  2. R.Wilkins, T.Saengsuwan, L.O'Shields, 'Short-circuit tests on current-limiting fuses: modeling of the test circuit', Proc. IEE, Vol. 140, No.1, pp. 30-36, 1993
  3. V.N.Narancic and G. Fecteau., 'Arc Energy and Critical Tests for HV Current Limiting Fuses', Int. Conf. on Electric Fuse and Their Applications, pp. 236-251, 1984
  4. O.Bottauscio et al., 'Influence of short circuit power factor on the cut off current of low voltage fuses', Int. Conf. on Electric Fuses and their Applications, pp. 201-205, 1991
  5. Ki-Dong Song, Byeong-Yoon Lee, Kyong-Yop Park, Jung-Hoo Park, 'Analysis Of Dielectric Recovery Characteristics for SF/sub 6/-Blast AFCe' , KIEE, Vol. 51-6, pp.273-284, 2002