Study on the Performance Optimization of Commercial Metal Hydride Refrigerator Powered by Exhaust Gas from Micro Gas Turbine

마이크로가스터빈의 부하에 따른 상용 수소흡장냉동기의 성능 최적화에 관한 연구

  • 김형식 (한국가스공사 연구개발원 이용기기연구센터) ;
  • 손화승 (한국가스공사 연구개발원 이용기기연구센터) ;
  • 최경식 (한국가스공사 연구개발원 이용기기연구센터)
  • Published : 2005.09.01

Abstract

MHR(Metal Hydride Refrigerator) powered by MGT exhaust gas is investigated to find out the optimum conditions corresponding to MGT operating powers. There are many factors to affect cooling capacity of MHR. In this study, the effect of switching time, flow rate of brine on cooling temperature and capacity is investigated. The present results show (1) hydrogen reaction is saturated with 25 min switching time at 25 kW MGT power, (2) cooling power shows maximum phenomenon with increasing switching time, (3) optimum switching times are 20 minutes for 15kW MGT power and 15 minutes for 20, 25kW MGT power, (4) according to increasing brine flow rate, cooling capacity shows decrease at 15 kW MGT power and changes little at above 20 kW MGT power.

Keywords

References

  1. Sohn, W. S. and Choi, K. S., 2003, Report for Development of Grid Connection Power Technology for on Site Type Micro Gas Turbine, Korea Gas Corporation
  2. Moto, D. and Jo, J. H., 2003, Cogeneration system between micro gas turbine and metal hydride refrigerator, J. of Korea Refrigeration and Air-Conditioning Industry Association, Vol. 81, pp.38-44
  3. Kwon, K. W. and Lee, J. Y., 1989, Optimum operating conditions of metal hydride chemical heat pump, J. of the Korean Hydrogen Energy Society, Vol. 1, No.1, pp.24-30