Abstract
In this paper the experiments of breakdown characteristics by temperature change of $SF_6$ gas, $SF_6$ liquid ($LSF_6$) and $N_2$ liquid ($LN_2$) in model GIS(Gas Insulated Switchgear) were described. From the experiments results, the breakdown voltage of $SF_6$ increases with the drop of temperature and the increase of the inner pressure in model GIS. The ability of $LSF_6$ insulation is higher than high-pressurized $SF_6$ gas and $LN_2$. The breakdown characteristics of $LSF_6$ were produced by bubble formed evaporation of $LSF_6$ and bubble caused by high electric emission. It is considered in this paper that the results are fundamental data for electric insulation design of superconductor and cryogenic equipments machine교 which will be studied and developed in the future.