Comparison of Thermal Comfort Performance Indices for Cooling Loads in the Lecture Room - An Correlation of PMV Bnd EDT -

강의실에서의 냉방부하에 따른 열쾌적성 평가지표 비교 - PMV와 EDT의 연관성 -

  • 노광철 (서울시립대학교 대학원 기계정보공학과) ;
  • 오명도 (서울시립대학교 기계정보공학과)
  • Published : 2005.07.01

Abstract

We performed the experimental and the numerical study on the comparison of thermal comfort performance indices for cooling loads in the lecture room for 4 cases: Fan coil unit(FCU) or 4-way cassette air-conditioner is respectively operated with the ventilation system or without. We measured the velocity, the temperature distribution and predicted mean vote(PMV) value in the lecture room for 4 different air-conditioning methods. Effective draft temperature(EDT) and PMV were investigated to analyze the characteristics of two thermal comfort indices in the lecture room and to compare their values each other. From the results we knew that there is the similarity between PMV values and EDTs when the room is air-conditioned for cooling loads. It turned out that definition of the control temperature is very important when the EDT is calculated. Finally EDT should not be used to predict the accurate thermal comfort in case that the temperature and humidity are suddenly varied and the zone affected by the solar and inner wall radiation.

Keywords

References

  1. Minister of Environment of Korea, 2003, 'The Act of Indoor Air Qualities for Multiple-Use Facilities,' Minister of Law of Korea
  2. Choi, J. M., Kim, Y. I. and Park, H. S., 2003, 'A Study on the Evaluation of Heating-Conditioned Environment with the Size of Classroom,' Journal of SAREK, Vol. 15, No. 12, pp. 1035-1042
  3. Kwon, Y. I. and Han, H. T., 2003, 'A Study on the Evaluation of the Air Change Efficiency of Multi-Air-Conditioner with Outdoor Air Intake for Heating Season,' Proceedings of the SAREK 2003 Winter Annual Conference, pp. 543-548
  4. Kim, K. H., Lee, K. S., Choi, H. S., Kang, T. W., Chung, B. Y. and Lee, G. G, 2003, 'A Study on the Indoor Thermal and Ventilation Characteristics in Office Building with Air-Conditioning and Ventilation System,' Proceedings of the SAREK 2003 Summer Annual Conference, pp. 1111-1116
  5. Cho, Y. J., 2001, 'ADPI Characteristics of Diffuser in a Room with Perimetric Heating Load,' Ph. D. Dissertation, Hanyang University
  6. Kim, S, H., Noh, K. C. and Oh, M. D., 2003, 'Study on the Evaluation Method of Thermal Comfort in Consideration of the Indoor Radiation Load,' Proceedings of the SAREK 2003 Winter Annual Conference, pp. 743-739
  7. Kim, K. H., Choi, H. S., Lee, G. G., Han, H. T. and Kwon, Y. I., 2004, 'The Characteristics of an Indoor Air Environment in Office with Location of Supply and Exhaust Diffuser,' Proceedings of the SAREK 2004 Summer Annual Conference, pp. 734-738
  8. ASHRAE Standard 55-92, 1991, 'Thermal Environmental Conditions for Human Occupancy,' ASHRAE, Atlanta, Georgia
  9. ISO 7730, 1994, 'Moderate Thermal Environments-Determination of the PMV and PPD Indices and Specification of the Conditions for Thermal Comfort,' ISO, Geneva
  10. ASHRAE Standard 113-1990, 1990, 'Method of Tseting for Room Air Diffusion,' ASHRAE, Atlanta, Georgia
  11. Patankar, S. V., 1980, Numerical Heat Transfer and Fluid Flow, Hemisphere, Washington, DC

Cited by

  1. The study on the effect of the solar radiation on thermal comfort and ventilation performance in room space vol.14, pp.1, 2016, https://doi.org/10.5407/JKSV.2016.14.1.019