Abstract
Malfunction by electrical surges is a serious problem on earth leakage current breakers(ELBs) used in a low voltage AC power system. In this paper, we tested ELBs according to IEC 61009-1 and KS C 4613 to analyze surge influence on ELB's malfunction. The test by application of surge voltage is specified both standards, but the test by application of surge current is specified only in IEC 61009-1. The experimental results showed that the ELBs used in this test are robust to surge voltage application, but the malfunction occurred to surge current application. Surge current is more frequent than surge voltage in actual situation. Therefore, ELBs should be tested by the surge current, and the domestic standard, KS C 4613, should includes a test procedure by the surge current application.
저전압 전력계통에 사용되는 누전차단기의 서지에 대한 오동작은 심각한 문제이다. 본 논문에서는 누전차단기의 서지에 대한 영향을 분석하기 위하여 IEC 61009-1와 KS C 4613 규격에 따라 누전차단기를 시험하였다. 서지전압 시험은 국내외 규격에 모두 적용되고 있으며, 서지전류 시험에 대해서는 국제규격 IEC 61009-1에만 규정되어 있다. 실험결과로부터 누전차단기는 서지전압에 대해서는 강인하지만 서지전류에 대해서는 오동작을 발생시켰다. 실제로 누전차단기가 설치되어 있는 환경에서는 서지전류의 침입이 빈번하므로, 누전차단기는 서지전류에 의한 오동작 시험이 수행되어야 하며, 국내규격에도 누전차단기 시험에 서지전류에 의한 평가를 포함하여야 할 것이다.