Abstract
In this paper, we took the basic experiment in order to explore the optical CT(optical current transformer) for measuring high current in a superhigh voltage condition. It is based on the faraday effect that changes the polarization characteristic of optical signals by the magnetic field. We used 1310[nm] laser diode for a light source and comprised a sensing part with the optional fiber of 5[m], 10[m], 20[m] length each. The range of current was from 400[A] to 1300[A]. We observed the characteristic of output that changes according to the length of the optical fiber composing the sensing part. The optical fiber of 5[m] length used for the sensing part had -11.1% of the maximum ratio of error and 10[m] and 20[m] length had -3.5% and 1.7% each. This means that the power and linearity of output increase in proportion to the length of optical fiber and applied current in the same experimental condition.
본 논문에서는 초고압 전력설비에서의 대전류 측정을 위한 광CT(optical current transformer)개발을 목적으로한 기초 연구를 하였다. 자기장에 의해서 광신호의 편광특성이 변화되는 Faraday 효과를 기본 이론으로 하며, 1310[nm] Laser Diode를 광원으로 사용하고 5[m], 10pm], 20[m]의 길이가 서로 다른 광섬유로 센싱부를 구성하였다. 전류의 측정은 400[A]에서 1300[A]까지의 범위에서 측정하였으며 센싱부를 구성한 광섬유의 길이에 따른 출력 특성을 파악하기 위한 실험을 하였다. 동일한 실험환경에서 각각의 출력의 크기 및 선형성은 인가 전류 및 광섬유의 길이에 비례하여 증가하였으며, 5[m]광섬유를 센싱부로 사용한 것은 최대 -11.1%의 오차율을, 10[m], 20[m]의 경우 각각 최대 -3.5%, 1.7%의 오차율을 나타냈다.