황토벽돌벽 주택의 실내온열환경에 관한 연구

A Study on the Indoor Thermal Environment of House Using Earth Brick Wall

  • 발행 : 2004.02.01

초록

The purpose of this study is to understand the indoor thermal environment in the earth brick wall building what is called a ecological Architecture. To investigate thermal performances of the earth brick walls, it measured indoor and outdoor air temperature, relative humidity, globe temperature and PMV in reference house. The result of this study were summarized as the followings; 1) When the outdoor average air temperature was $21.8^{\circ}$, livingroom was $24.9^{\circ}$, kitchen was $25.1^{\circ}$ and 2nd floor room was $25.6^{\circ}$ at 150 cm height from the floor. 2) Although the average outdoor relative humidity was 78%, the livingroom was 67.5%. 3) As the air temperature difference between at the top and bottom was $0.6^{\circ}$ in living room, this value was below 1 % of PPD by ASHRAE Handbook. 4) Predicted Mean Vote(PMV) by ISO-7730 was +0.41.

키워드

참고문헌

  1. 한국주거학회논문집 v.14 no.3 공동주택의 냉방시 실내온열 환경평가 연구 김난행;안병욱
  2. 한국주거학회논문집 v.14 no.5 바닥복사난방의 실별제어시스템에 관한 열성능 평가 석호태(외)
  3. 전통환경형 농촌주택의 모형개발연구 농림부
  4. 대한건축학회지 흙과 인간환경 이경희
  5. 한국농공학회 전통 흙집 벽 재료의 특성 분석 리신호;송창섭;오무영
  6. 대한건축학회 논문집 PMV지표에 의한 건물에서의 온열환경 특성에 관한 연구 손장열;백용구;서기석
  7. 대한건축학회 논문집 흙건축의 생태적 의미와 현대적 이용에 관한 연구 박정식(외)
  8. ASHRAE Handbook Fundamental ASHRAE
  9. 토질역학 R.F.Craig