This paper develops an ADWHM(Advanced Digital Watt-Hour Meter) which integrates and implements the voltage management data record function and the load management data record function in the electronic watt-hour meter. ADWHM is developed based on PIC16F874 which is 8bit micro-controller of RISK type for the easy of programing and maintenance, and electronic power signal processing module is located at front of it to reduce the computing load of processor. Also, a 16kbyte EEPROM is used to record the voltage management data and load management data for a week as well as watt-hour data and USART communication mode is used to transfer data from ADWHM to PC. The accuracy of the voltage and unt measuring for ADWHM is verified by identifying the LCD display values of the ADWHM after the voltage signals of id levels from digital function generator is applied to PT(Potential Transformer) and CT(Current Transformer) output under state which it is separated from real power line. On the its basic functions such as watt-hour data recording function, voltage management data recording function and load management data recording function was verified by showing data for three days among the collected data to PC by RS232C communication from ADWHM which was connected to real power lines for a week.

키워드

참고문헌

  1. Cameron L. Smallwood, 'Power Quality Issues Reading to Power Line Carrier Automated Meter Reading', Proceedigns of the 2001 Rural Electric Power Conference, B1-1-8, April 2001 https://doi.org/10.1109/REPCON.2001.949513
  2. S.T.Mak, D.Radford, Sioe T.Mark, Denny Radford/ 'Design Considerations for Implemetation of Large Scale Automatic Meter Reading/Added Utilization Coasts Associated with Different Communication Architectures for Distribution Automation and Demand Side Management/', IEEE Power Engineering Review, Vol. 15, No.1, Jan. 1995 https://doi.org/10.1109/61.368410
  3. Newbury J. Miller W, 'Multiprotocol Routing for Automatic Remote Meter Reading using Power Line', IEEE Transations on Power Delivery, Vol. 16, No.1, pp 1-5, Janu. 2001 https://doi.org/10.1109/61.905567
  4. Frigui I, Stone R, Alfa AS,' Message for a Priority-Based Automatic Meter Reading Network', Computer Communications, Vol.20, No.1, 1997년 https://doi.org/10.1016/S0140-3664(96)01167-X
  5. S. Mar and D. Radford,'Design Considerations for Implementation of Large Scale Automatic Meter Reading', IEEE Transactions on Power Delivery, Vol.10 No.1, pp 97-103, Jan. 1995 https://doi.org/10.1109/61.368410
  6. 고윤석, 윤철수, 김관호, 윤상문, 서성진, '배전원격관리를 위한 차세대 디지털 적산전력계 설계,'2002년도 대한전기학회 하계학술대회발표논문집, 2002. 7
  7. 고윤석, 윤철수, 김관호, 윤상문, 서성진,'차세대 디지털 적산전력계에 기반한 배전원격관리 시스템 설계', 2002년도 대한전기학회 하계학술대회발표논문집, 2002. 7
  8. 고윤석, 윤상문, 서성진,'차세대 디지털 적산전력계 개발',2003년도 대한전기학회 하계학술대회발표논문집, 2003. 07