3상 위상제어 정류기에서 DVR의 응답시간과 허용 가능한 순시저전압의 범위에 대한 연구

A study on the permissible range of voltage dips and the response time of DVR in 3-phase phase-controlled rectifier

  • 발행 : 2004.04.01

초록

It is investigated that the relation between the response time of DVR(Dynamic Voltage Restorer) and the possible compensation range of voltage dip by the DVR system which protects the 3-phase phase-controlled rectifier from voltage dip. As a result, the permissible range of voltage dip is presented in the 3-phase phase-controlled rectifier, and it is presented that the range of voltage dip which can be compensated according to the DVR s response time. when the DVR compensates voltage dip, Using the proposed method, the DVR s response time can be determined from the parameters of 3-phase phase-controlled rectifier and the possible compensation range of voltage dip, and it is possible to use the control system which have an appropriate speed. Therefore, the use of excessively fast device can be avoided, and the stability of the overall system is improved. Also the reliance of DVR about the 3-phase phase-controlled rectifier can be verified.

키워드

참고문헌

  1. A. Arora, K. Chan, T. Jauch, A. Kara, and E. Wirth, 'Innovative system solutions for power quality enhancement,' ABB review, pp. 4-12, March 1998
  2. M. H. J. Bollen, 'Voltage sags: effects, mitigation and prediction,' Power Engineering Journal, vol. 10, pp. 129-135, June 1996 https://doi.org/10.1049/pe:19960304
  3. S. S. Choi, B. H. Li, and D. M. Vilathgamuwa, 'Dynamic voltage restoration with minimum energy injection,' IEEE Transactions on Power Systems, vol. 15, no. 1, pp. 51-57, February 2000 https://doi.org/10.1109/59.852100
  4. C. Zhan, C. Fitzer, V. K Ramachandaramurthy, A. Arulampalam, M. Barnes, and N. Jenkins, 'Software phase-locked loop applied to dynamic voltage restorer (DVR),' Power Engineering Society Winter Meeting 2001 IEEE, vol. 3, pp. 1033-1038, February 2001 https://doi.org/10.1109/PESW.2001.917210
  5. S. S. Choi, B. H. Li, and D. M. Vilathgamuwa, 'Design and analysis of the inverter-side filter used in the dynamic voltage restorer,' IEEE Transactions on Power Delivery, vol. 17, no. 3, pp. 857-864, July 2002 https://doi.org/10.1109/TPWRD.2002.1022815
  6. C. Fitzer, M. Barnes, and P. Green, 'Voltage sag detection technique for a dynamic voltage restorer,' IAS Annual Meeting, vol. 2, pp. 917-924, Oct. 2002
  7. M. Vilathgamuwa, A. A. D. Ranjith Perera, and S. S. Choi, 'Performance improvement of the dynamic voltage restorer with closed-loop load voltage and current-mode control,' IEEE Transactions on Power Electronics, vol. 17, no. 5, pp. 824-834, Sept. 2002 https://doi.org/10.1109/TPEL.2002.802189
  8. J. Arrillaga, N. R Waston, and S. Chen, Power System Quality Assessment, John Wiley & Sons, 2000
  9. M. H. J. Bollen, 'Voltage, power and cwrent ratings of series voltage controllers,' Power Engineering Society Winter Meeting 2000 IEEE, vol. 4, pp. 2910-2915, January 2000 https://doi.org/10.1109/PESW.2000.847347
  10. C. Becker, W. Braun Jr., K Carrick, T. Diliberti, C. Grigg, J. Groesch, B. Hazen, T. lmel, D. Koval, D. Mueller, T. St. John, and L. E. Comad, 'Proposed chapter 9 for predicting voltage sags (dips) in revision to IEEE Std 493, the Gold Book,' IEEE Transactions on Industry Applications, vol. 30, no. 3, pp. 805-821, May/June 1994 https://doi.org/10.1109/28.293731
  11. E. W. Gunther and H. Mebta, 'A survey of distribution system power quality-preliminary results,' IEEE Transactions on Power Delivery, vol. 10, no. 1, pp. 322-329, January 1995 https://doi.org/10.1109/61.368382
  12. S. Polmai, T. Ise, and S. Kumagai, 'Experiment on voltage sag compensation with minimum energy injection by use of a micro-SMES,' IEEE PCC-Osaka 2002, vol. 2, pp. 415-420, April 2002 https://doi.org/10.1109/PCC.2002.997554