Human Hazard by Outdoor Electrical Facilities in Submerged Area

옥외 전기시설물 침수시 누설전류에 의한 인체영향

  • 하태현 (한국전기연구원 지중시스템연구그룹) ;
  • 이현구 (한국전기연구원 지중시스템연구그룹) ;
  • 배정효 (한국전기연구원 지중시스템연구그룹) ;
  • 김대경 (한국전기연구원 지중시스템연구그룹)
  • Published : 2003.12.01

Abstract

We show three-dimensional distribution of voltages resulted from the leakage current originated from outdoor electrical facilities in a submerged area. In case these facilities are grounded by the neutral line multiple grounding method, the existence of ungrounded electrical facilities can cause a disastrous effect on near-by passengers. In order to investigate this situation, we installed a real-scale test field for the experiment type I (for the leakage current path between a enclosure grounded electrical facility and another enclosure grounded one), and that for the experiment type II (for the leakage current path between a enclosure grounded electrical facility and another ungrounded one). For both cases, we carried out three-dimensional monitoring of the voltage distribution while varying additional conditions such as the exposure of the underground cables and the finishing of cable connection part. The result shows that a disastrous effect on human safety can arise from the leakage current without a pertinent measure for the construction and maintenance of outdoor electrical facilities.

Keywords

References

  1. KWIKGRID${\circle}R$, Computer Software, Ground-it.com Consulting Ltd., 2001
  2. IEEE STD 80-2000, IEEE Guide for Safety in AC Substation Grounding
  3. CDEGSTM, Resistivity, Grounding, Cable & Line Parameters, Fault Current Distribution, Electrical Interference and Electromagnetic Fields Analysis Software, Safe Engineering Services & Technologies Ltd.
  4. John,C. DAVIS, 'Statistics and Data Analysis in Geology', 2nd Edition, John Wiley & Sons, 1986
  5. JEA G8101-1971, 저압전로지락보호지침