Abstract
This paper presents leakage magnetic field and leakage inductance calculations in current transformer by means of 3-D Integral methods. From the distribution diagram of leakage magnetic flux to be analyzed using program called TRACAL 3, ti confirms a parallel to the winding axis direction of the leakage flux lines in the air gap between the windings. The leakage inductances L$\sub$r1/ and L$\sub$r2/ of the primary and secondary winding were calculated, their values are 4.23 MH and 0.49 mH, respectively. They are also similar to the measured values of he leakage inductances of the experimental verification, 4.06 mH and 0.47 mH.