Abstract
This study investigated heat transfer characteristics of refrigeration system using new type aluminium heat transfer tube for evaporator of refrigeration and air-conditioning comparing with bare tube. From the result of heat transfer experiment form one phase flow using cooled and hot water, about 20% heat transfer performance is superior in case of same quantity of flow and about 4% heat transfer performance if superior in case of same velocity comparing with bare tube. Casing of two phase flow, heat transfer performance of new type aluminum heat transfer tube shows about 50% superior heat transfer performance comparing with bare tube in the same evaporating pressure when using heat transfer tube as evaporator and shows about 47% increase when expressing performance coefficient as the rate of refrigerating capacity and compressing work. However, it can be known that pressure drop in the heat transfer tube is taken higher value of about 18% in case of new type aluminum heat transfer tube. From the above result, new type aluminum heat transfer tube is excellent comparing with bare heat transfer tube using the existing heat exchanger for refrigerator.