Abstract
This paper proposes a fuzzy decision making method for power transformer protection to identify an internal fault from other transient states such as inrush, over-excitation and an external fault with current transformer (CT) saturation. In this paper, analyzing over 300 EMTP simulations of disturbances, four input variables are selected and fuzzified. At every sampling interval from half to one cycle after a disturbance, from the EMPT simulations, different fuzzy rule base is composed of twelve if-then fuzzy rules associated with their basic probability assignments for singleton- or compound-support hypotheses. Dempster's rule of combination is used to process the fuzzy rules and get the final decision. A series of test results clearly indicate that the method can identify not only an internal fault but also the other transients. The average of relay operation times is about 12(ms). The proposed method is implemented into a Digital Signal Processor (TMS320C31) and tested.