Abstract
Corrosion of rebars can occur if there are cracks, moisture and availability of oxygen or carbonation proceeds, chloride penetrates and diffuses in concrete. Once rebars in concrete corrodes, subsequently accompanied with scaling, spalling in concrete cover. As a result of them, the RC structure is seriously deteriorated. In this study, theoretical review and experiments for cathodic protection(CP) have been performed to control corrosion of rebars in concrete contained chlorides and pre-crack. For CP the impressed current system was applied, the protection effect was investigated when rebars was directly contacted with salt water due to crack and open to much chlorides in concrete. In order to investigate the effect of protection, when CP was energized for 1 year, half-cell potential, potential-decay with current density, corrosion ratio, etc. were measured. With the cathodic protection by impressed current system, the depolarized values of all specimen were met NACE Standard, the effect of 34~84% of the ratio of corrosion area and 84~86% of cross-section reduction were calculated.
콘크리트 구조물에 균열이 생겨 물과 산소의 침투확산이 용이해 지거나 또는 외부로부터 염소이온과 같은 염화물이 침투확산되어 콘크리트 중의 철근까지 도달할 경우 및 콘크리트의 중성화가 철근위치까지 진행될 경우 철근의 부동태 피막은 파괴되어 부식이 급진전 되며 콘크리트의 박리 및 탈락현상이 수반될 뿐만 아니라 구조물의 내구성이 크게 저하된다. 본 연구에서는 콘크리트 중의 철근부식을 억제하기 위한 한 방안으로 적용되는 전기방식의 이론적인 고찰과 콘크리트 내부에 다량의 염화물을 함유시키거나 또는 균열을 발생시킨 시험체에 대하여 외부전원법을 활용한 실내실험을 실시하여 철근의 방식효과에 대해 고찰하였다. 외부전원법에 의한 전기방식을 실시하여 복극량을 측정한 결과 대상 시험체 모두 NACE의 방식기준을 만족하였으며, 부식면적율의 측정결과 34 ~84%, 단면감소의 경우 84 ~ 86%의 방식효과를 확인하였다.