Partial Discharge Detection for the Power Cables using AC and Oscillating wave Voltage

전력케이블에서 교류전압과 진동파 전압을 이용한 부분방전 측정

  • Published : 1999.04.01

Abstract

In this paper, in order to investigate availability of the OW-PD measurement method which has been proposed as an alternative of AC-PD measurement method to an after laying test and/or diagnosis for the power cable system, partial discharges owing to the needle-type defect integrated into the cable have been measured using AC and OW(Oscillating Wave) voltages. In the AC-PD measurement, the magnitude, phase and pulse number of partial discharges have been changed with the duration of voltage application, which can be analyzed through the relation with the process of the electrical tree initiation and propagation. In addition, the characteristics of partial discharges using OW voltage are appeared to be similar to those in case of AC-PD measurement and to be different with the shapes of electrical tree. From these results, it is concluded that the OW-PD measurement method is available to the tests for the cable system.

Keywords

References

  1. CIGRE, 1996-Session, 15/21/33-12 Test After Laying, Diagnostic Testing using Partial Discharge Test at Site E.Pultrum (et al.)
  2. 한선 전력연구원 연구보고서 95YJ17 지중배전선로의 준공시험기술 및 접속재 진단기술 개발 구자윤(외)
  3. 8th ISH PD-Detection and Localization using Unipolar Impulse Voltage for On-Site Testing of Polymer Insulated Cables I. Krage;W. Kallkner
  4. CIGRE, Paper 1020-02 On-Site Testing of Extruded Power Cables by PD Measurement at SI Voltage Lemke E.;Roding R.;Weissenberg W.
  5. 7th ISH, Paper 75.07 PD Phenomena in Polyethylene under AC and Impulse Stresses with respect to On-Site Diagnosis Tests of Extruded Cables Lemke E.;Friese G.
  6. 대한전기학회 96하계학술대회 충격파-부분방전(SI-PD) 시험방법을 이용한 케이블 진단에 관한 기초 연구 김정태(외)
  7. 9th ISH, 5617-1 Complex Discharge Analyzing (CDA) - an Alternative Procedure for Diagnosis Tests on HV Power Apparatus of Extremely High Capacity E.Lemke;P.Schmiegel
  8. 대한전기학회 98 방전 및 고전압연구회 춘계학술발표회 논문집 진동파를 이용한 22.9kV 지중전력케이블의 부분방전 특정기술 개발 김정태(외 3인)
  9. 대한전기학회 논문지 v.47 no.4 진동파 전압을 이용한 22.9kV CN/CV 전력케이블의 준공검사에 관한 연구 구자윤(외)