Dehumidification and Evaporative Cooling Efficiency by Water Pipes in Greenhouse
냉수파이프에 의한 온실의 제습 및 증발냉각효율
Abstract
Greenhouse crop production under critical summer climate In Korea has considerable difficulties because of high temperature and relative humidity. In this study, some water pipes were tested as a means of the dehumidification and increment of evaporative cooling efficiency. As a result of heat transfer characteristic analysis, overall heat transfer coefficient of copper pipe was larger than steel pipe, and estimated values were smaller than measured values. The condensed quantities of vapor were not significantly different between copper pipe and steel pipe, however dehumidifying effect by the water pipes was significantly large. It was estimated based on the results that the evaporative cooling system by the water pipe will be able to increase the evaporative cooling efficiency of about 48%, and decrease the temperature of about 1.3
극심한 고온으로 인해 정상적인 작물의 재배가 어려운 여름철의 온실 내 기온을 억제시키기 위한 방법 중 가장 효율을 인정받고 있는 증발냉각법은 실내 습도의 증가로 인해 그 사용에 제한을 받게 된다. 본 연구에서는 온실에서 증발냉각법의 냉방효율을 높이기 위한 방법으로 냉수파이프를 설치하여, 그 열적 특성을 분석하고, 제습효과를 조사하였으며, 그 결과를 요약하면 다음과 같다. 동파이프와 아연도금스틸파이프의 총열전달량을 비교한 결과, 동파이프가 다소 크게 나타났으나, 유의성이 없었으며, 두 가지 파이프 모두 이론값 보다 실측값이 더 작게 나타났다. 냉수파이프 표면에 응축되어 제거된 수증기의 양은 동파이프와 아연도금스틸파이프 사이에서 큰 차이를 보이지 않았으나, 두 가지 파이프 모두에서 제습효과는 충분히 큰 것으로 나타났다. 냉수파이프를 설치함으로써 증발냉각시스템의 냉방효율을 평균 48%만큼 높일수 있으며, 평균 1.3