정풍량방식 덕트에서 이중압력측정방법을 이용한 취출구 풍량조정
Balancing air flow at terminal in CAV duct system with DPM method
초록
Adequate ventilation with the proper amount of air to the right place is important factor to achieve a good Indoor air climate. Thus it is of prime importance that the ventilation system is working properly. This requires reliable pressure loss calculation to balance the air flow through duct systems. So a computer program for balancing CAV duct system is developed In this study. The results of CAV duct system is compared with the "Balans" code developed by Larsen from Norway. To obtain the pressure drop characteristics of damper at duct terminal, some experiments are performed using DPM(Dual Pressure Measurement) system. To adjust the resistance of damper, present study suggests that some special diffusers should be designed and damper producers should give the data of air flow vs. pressure drop to the customs when they manufacture the damper. One of the results concludes that the working time can be reduced from several minutes to several seconds per damper in the present experimental site, if the DPM system and the air volume adjusting process are used.