Abstract
The purpose of this study is to investigate the breakdown properties in joint interface of power cables with heat treatment. The specimens have the structure of XLPE/EPDM interface like the joint of distribution power cable. The breakdown characteristics of the SLPE/EPDM joint were studied with crosslinking by=products. AC breakdown voltages were measured with heat treatment time and interfacial materials and crosslinking by-products as testing factors. This study has shown that crosslinking by-product gases play an important role at the insulation properties of cable joints by heating. The dielectric strength shows the lowest values at 4 hours heat treatment. The AC breakdown strength in the untreated sample was increased with heat treatment time.