Some Considerations on the Capacity Estimation of Emergency Electric Generator in Apartment Complex

공동주택의 비상발전기 용량산정방식에 관한 고찰

  • 김정태 (대진대학교 전기공학과) ;
  • 이욱 (대진대학교 전기공학과)
  • Published : 1996.08.01

Abstract

In this study, for the capacity estimation of emergency electric generators built in apartment complex using NEGA C 201 method, it was proposed application methods of simultaneously starting groups and demand factors. Also, it was suggested that capacities of the electric generator might be calculated for two kinds of electric facilities; one is loads for the convenience of tenants when main electric supply cuts off, and the other is loads for fire. For 7 apartment complex of large-size (about 1, 500 households), medium- size (about 1, 000 households) and small - size (about 500 households), electric generator capacities were calculated and electric power were measured. Through the comparison between calculated values and measured values, it could be proved the suitability of these application methods. In addition, the calculated electric generator capacities were appeared to fit into engin capacities by NEGA C 201 method as well as those by conventional method.

본 연구에서는 공동주택에 설치되는 비상발전기의 용량산정 방식에 대하여, NEGA C 201 방식을 적용할 때 필요한 동시시동그룹의 구성과 수용률의 적용 방법을 제시하였으며, 대상부하를 "정전시 부하"와 "화재시 부하"로 구분하여 계산할 것을 제안하였다. 아울러, 500호~1,500호 정도의 대.중.소 규모 공동주택 단지를 대상으로 비상발전기의 용량을 산출하고 실측 결과와의 비교를 통해 본 연구의 제시 방안이 타당함을 입증하였다. 또한, 본 연구에 의한 비상발전기 설계용향은 NEGA C 201 방식에 의한 엔진용량 및 기존방식에 의한 엔진용량과 잘 적합되는 것으로 나타났다.용량과 잘 적합되는 것으로 나타났다.

Keywords

References

  1. 인버터승강기의 동력설비 용량산정 및 고조파해석에 관한 연구 대한주택공사
  2. 防災電氣ハンドブツク 東京電機大學
  3. 電氣設備工事設計·施工マニュァル 電氣設備工學會
  4. 건축전기설비 지철근
  5. 전기 통신 설계 지침서 대한주택공사
  6. シリ-ズ解設 最近の 消防法 および同政令 規則に 關する 通知 (その1) no.1989년 3월 日本 電氣工業
  7. 自家發電設備の 出力算定に 關する 100號通知の 一部改正について no.1990년 8월 日本 電氣工業
  8. 自家發電設備 出力算定法解設書(Q & A 付) 社團法人 日本內然力發電設備協會
  9. デイ-ゼルェンソンソ 驅動陸用 同期發電機 JEM-1354 日本 電氣工業協會規格
  10. 에너지 절감을 위한 전동력의 고효율 운전제어 연구 대한주택공사
  11. 디젤엔진 구동 육상용 동기발전기 KEMC1111 한국 전기공업협동조합