Abstract
In this study, for the capacity estimation of emergency electric generators built in apartment complex using NEGA C 201 method, it was proposed application methods of simultaneously starting groups and demand factors. Also, it was suggested that capacities of the electric generator might be calculated for two kinds of electric facilities; one is loads for the convenience of tenants when main electric supply cuts off, and the other is loads for fire. For 7 apartment complex of large-size (about 1, 500 households), medium- size (about 1, 000 households) and small - size (about 500 households), electric generator capacities were calculated and electric power were measured. Through the comparison between calculated values and measured values, it could be proved the suitability of these application methods. In addition, the calculated electric generator capacities were appeared to fit into engin capacities by NEGA C 201 method as well as those by conventional method.
본 연구에서는 공동주택에 설치되는 비상발전기의 용량산정 방식에 대하여, NEGA C 201 방식을 적용할 때 필요한 동시시동그룹의 구성과 수용률의 적용 방법을 제시하였으며, 대상부하를 "정전시 부하"와 "화재시 부하"로 구분하여 계산할 것을 제안하였다. 아울러, 500호~1,500호 정도의 대.중.소 규모 공동주택 단지를 대상으로 비상발전기의 용량을 산출하고 실측 결과와의 비교를 통해 본 연구의 제시 방안이 타당함을 입증하였다. 또한, 본 연구에 의한 비상발전기 설계용향은 NEGA C 201 방식에 의한 엔진용량 및 기존방식에 의한 엔진용량과 잘 적합되는 것으로 나타났다.용량과 잘 적합되는 것으로 나타났다.