Modeling and verification of generator/control system of Seo-Inchon combined-cycle plant by load rejection test

부하차단시험에 의한 서인천복합화력 발전기.제어계의 모델링 및 검증

  • 최경선 (한국전기연구소 전력계통연구부 시스템제어연구팀) ;
  • 문영환 (한국전기연구소 전력계통연구부 시스템제어연구팀) ;
  • 김동준 (한국전기연구소 전력계통연구부 시스템제어연구팀) ;
  • 추진부 (한국전력공사 전력연구원) ;
  • 류승헌 (한국전력공사 전력연구원) ;
  • 권태원 (한국전력공사 전력연구원)
  • Published : 1996.04.01

Abstract

The gas-turbine generator of Seo-Incheon combined-cycle plant was tested for derivation of a model for dynamic analysis. Load rejection and AVR step test was performed to get the dynamic response of generator. The parameters of generator/control system model were determined by these measured data. No-load saturation test was performed for the saturation characteristics of the generator under steady state. V-curve test was also performed so as to find exact generator parameters. Q-axis parameters of generator was derived by measuring power angle. AVR and governor constants have been tuned by their oscillatory period and setting time characteristics. The derived parameters of generator control system is verified by one-machine infinite bus system simulation. (author). 7 refs., 20 figs., 5 tabs.

Keywords