Preventive diagnosis of the power transformer by the moving average of ultrasonic signal number

超音波 信號 數의 移動平均에 의한 電力用 變壓器 豫防診

  • 권동진 (한전 전력연구원 전력연구실) ;
  • 곽희로 (숭실대 공대 전기공학과) ;
  • 정상진 (한전 전력연구원 전력연구실) ;
  • 김정부 (한전 전력연구원 765kV 송전기술연구팀)
  • Published : 1996.03.01

Abstract

This paper describes a diagnostic technique of power transformers by on-line detection of ultrasonic signals. A trend of partial discharge variation in a real transformer was estimated by counting the number of ultrasonic signals until insulation paper in the point-to-plane electrode is punctured. The number of electrical signals is closely related to the ultrasonic signals generated by partial discharge. The trend of the ultrasonic signal number could easily be distinguished by taking moving average. The insulation failure due to partial discharge in transformers can be predicted based on the trend analysis of ultrasonic signal number caused by partial discharge. (author). 14 refs., 10 figs.