설비공학논문집 (Korean Journal of Air-Conditioning and Refrigeration Engineering)
- 제6권1호
- /
- Pages.47-53
- /
- 1994
- /
- 1229-6422(pISSN)
- /
- 2465-7611(eISSN)
R22의 대체냉매를 사용한 공기조화기의 성능 시뮬레이션
Cycle Simulation of the Air-Conditioner Using Alternatives to R22
초록
Cycle simulation of the air-conditioner was carried out using a number of candidate alternatives to R22;R32/R125/R134a(30/10/60, by mass percent), R32/R125/R134a(10/70/20), R32/R134a(25/75), R32/R134a(30/70), R32/R125(60/40), R290(propane) and R134a. In this study, we considered only the basic parts of the air-conditioner such as the compressor, the evaporator, the condenser and the capillary tube, for the purpose of analysis. The performance characteristics of alternatives considered here were examined by comparing with the case using R22 at the constant volumetric flow rate condition. The results of our analysis revealed that the use of refrigerant mixtures, R32/R134a(30/70) and R32/R125/R134a(30/10/60), was appropriate for the alternatives to R22 in view of the cooling capacity and the COP. For the case of using R134a and R290, the COP was observed to increase under the same volumetric flow rate condition, but the cooling capacity was substantially decreased. Therefore the use of R134a and R290 should be accompanied with increasing considerably the size of compressor in order to maintain the same cooling capacity of R22.
키워드