The Effect of Operating Conditions on the Frost Formation in a Vertical Plate at a Low Temperature

저온 수직평판에서 착상에 대한 운전조건의 영향


Abstract

In this study, the influence of a frost formed on the vertical plate for different operating conditions(the temperature of the air, the humidity of the air, the velocity of the air, and the temperature of the cooling plate) is investigated. The performance of the heat exchanger is examined by introducing a parameter such as the energy transfer resistance. Correlations which relate frost density, frost thickness and energy transfer resistance to Reynolds number, air temperature and humidity, and cooling plate temperature are developed. Static pressure drop and air flow rate are expressed as a function of free flow area of air.

Keywords