Condensation Heat Transfer Characteristics of HCFC - 123 inside Horizontal Smooth Tube

HCFC-123의 수평 평활관내 응축 전열 특성에 관한 연구

  • Published : 1993.06.01

Abstract

Experimental data on the heat transfer characteristics of HCFC-123 and CFC-11 during condensation in horizontal smooth tube are presented. The experimental apparatus consisted of a closed working fluid loop, coolant loop, and measuring system. The major components of the working fluid loop made of a refrigerant pump, boiler, superheater, refrigerant flow meter, receiver and test section. The tube-in-tube type test section was made of smooth tube which were constructed form 9.52 mm outer diameter of smooth copper tube with 50 mm outside diameter of PVC tube duct. The ranges of parameter, such as refrigerant mass velocity, coolant flow rate, and quality were 90-325kg/($m^2$.s), 60-360kg/h, 5-95% respectively. Data were obtained under steady state condition for annular flow. As a result of these, the condensation heat transfer coefficients for HCFC-123 were slightly lower than those of CFC-11 from 8% to 15% inside horizontal smooth tube. Furthermore, a new generalized correlation for the heat transfer coefficients of HCFC-123 and CFC-11 during condensation inside horizontal smooth tube is proposed.

Keywords