Abstract
The second kind LiBr-$H_2O$ absorption heat pump system was simulated and the performances of it were predicted. The elements of heat pump system, evaporator, absorber and generator were analysed by solving the energy balance equations and concentration equations which describe the reactions between working fluids. The results show that the temperature gain of absorber is affected considerably by the operating conditions of heat pump system, on the other hand, COP is little affected by them.