Abstract
This study simulates a typical solar system using the transient simulation program TRNSYS, and calculates the maximum cooling load of the model room of $50m^2$. In this study, energy rate control method is used in calculating a maximum cooling load. On the ground of the maximum cooling load of the model room, the variables that have an effect on the solar collection performance of the solar system are made a selection. Also in this study the trend of the solar collection performance is shown as the variables change. The results show that the variables which have an effect on the collection performance are collector area, collector mass flow rate, collector slope and the volume of storage tank, and the optimal value of Ac/Vt is not constant but varies as the collector area and the collector mass flow rate. Also the results show that for cooling system the optimal value of the collector slope is latitude minus $15^{\circ}$ during the seasonal operations, and twenty percent of the maximum cooling load is saved with the aid of the solar energy.