계통연계 인버터를 위한 새로운 고조파 보상법

A Novel Harmonic Compensation Technique for the Grid-Connected Inverters

  • 발행 : 2019.07.02

초록

The output current of the Grid Connected Inverter (GCI) can be polluted with harmonics mainly due to i) dead time in switches, ii) non-linearity of switches, iii) grid harmonics, and iv) DC link fluctuation. Therefore, it is essential to design the robust Harmonic Compensation (HC) technique for the improvement of output current quality and fulfill the IEEE 1547 Total harmonics Distortion (THD) limit i.e. <5%. The conventional harmonic techniques often are complex in implementation due to their i) additional hardware needs, ii) complex structure, iii) difficulty in tuning of parameters, iv) current controller compatibility issues, and v) higher computational burden. In this paper, to eliminate the harmonics from the GCI output current, a novel Digital Lock-In Amplifier (DLA) based harmonic detection is proposed. The advantage of DLA is that it extracts the harmonic information accurately, which is further compensated by means of PI controller in feed forward manner. Moreover, the proposed HC method does not require additional hardware and it works with any current controller reference frame. To show the effectiveness of the proposed HC method a 5kW GCI prototype built in laboratory. The output current THD is achieved less than 5% even with 10% load, which is verified by simulation and experiment.

키워드