건축물 창호의 화재안전설계를 위한 실험적 연구

An Experimental Study on the Fire Safety Design of Windows in Building

  • 이병흔 (호서대학교 소방방재학과) ;
  • 진승현 (호서대학교 소방방재학과) ;
  • 한지우 (호서대학교 소방방재학과) ;
  • 권영진 (호서대학교 소방방재학과)
  • 발행 : 2018.05.16

초록

In the building, the opening penetrates the wall and serves as a spreading channel for smoke and flame in case of fire. In Korea, more than 1,500 fire plume are generated annually, and the number has increased by about 30% over the past five years. Therefore, in the case of windows protecting the opening, fire protection performance is important to prevent the spread of fire. However, in Korea, the standard for window is not clear. In this study, fire tests (EN 13823) for windows were conducted in Korea, and then fire protection performance of windows was compared. As a result of the experiment, PVC windows showed a phenomenon that they could not withstand the temperature during the fire experiment, and AL windows showed a difference in the degree of cracking of the glass.

키워드