Heating Performance Analysis of Building Integrated Geothermal System
건물일체형 지열히트펌프시스템의 난방 성능 분석
- Jin, Shangzhen (Dept. of Architectural Engineering, Graduate School, Yonsei University) ;
- Lee, Jin-Uk (Research Institute of Science and Technology of POSCO, POSCO Global R&D Center) ;
- Kim, Tae-Yeon (Dept. of Architectural Engineering, Yonsei University) ;
- Leigh, Seung-Bok (Dept. of Architectural Engineering, Yonsei University)
- Published : 2012.03.29
Abstract
Ground source heat pump is a central heating and cooling system that pumps heat to or from the ground. Building Integrated Geothermal system used in this experiment is one of the Ground Source Heat Pump Systems which utilize energy pile. The purpose of this study is to evaluate heating performance of the system. The building is a low-energy experiment apartment in Yonsei University Songdo Campus and the subject is one of the energy reduced houses in this apartment. In the experiment, indoor temperature, outdoor temperature and the inlet and outlet temperature of ground heat exchanger and subject model, were measured. Then the heat pump's Coefficient of performance(COP) of the heat pump was calculated. As a result, the COP of heat pump is 4-5. Although the depth of the ground heat exchanger in this experiment is shallower than usual heat exchanger, the result of heating performance of this system was good as well.
Keywords
- Building Integrated Geothermal System;
- Ground Source Heatpump System;
- Energy Pile;
- Ground Heat Exchanger;
- Heat Pump;
- Coefficient of Performance
- 건물일체형 지열시스템;
- 지열히트펌프 시스템;
- 에너지 파일;
- 지중열교환기;
- 히트펌프;
- 성능계수COP;