Analysis on Heat of Hydration for Height of Shell Concrete Pouring in Reactor Containment Building

원자로건물 외벽 타설 높이 산정을 위한 수화열 해석

  • Published : 2012.11.16

Abstract

A thermal stresses by heat of hydration was analyzed according to a change of a pour height in reactor containment building. In case of more than 3.6m pouring height a crack index by heat of hydration analysis resulted in less than 1 because there is not a construction joint of vertical direction and for a self-restraint effect of circumferential section shape. Therefore detailed consideration on a mixture proportion of binder type, quantity in concrete and selection of a form in seasonal air temperature is needed for a control of tensile stress by heat of hydration.

Keywords