Effect of heat pump performance improvement by use of thermal tank with temperature seperation plate

격판분리 축열조의 히트펌프 성능개선 효과

  • 문종필 (농촌진흥청 국립농업과학원) ;
  • 이성현 (농촌진흥청 국립농업과학원) ;
  • 권진경 (농촌진흥청 국립농업과학원) ;
  • 강연구 (농촌진흥청 국립농업과학원) ;
  • 이수장 (농촌진흥청 국립농업과학원)
  • Published : 2011.05.26

Abstract

This study was carried out in order to estimate the effect of heat pump performance by use of thermal tank with 3 seperation plates which were able to divide thermal tank into 3 chambers that have different temperatures levels. For testing the effect of developed thermal tank which was installed for supplying the heat to the paprika greenhouse in Jinju city. The volume of thermal storage tank was designed for $110m^3$ which was able to cover 30% of heating capacity. The temperature difference was 3 degree Celcius between high temperature and low temperature when only heating circulation was made from heat pump to thermal tank. but 5.5 degree Celcius difference was made when heating circulation of heat pump to thermal thank and hot water supplying circulation of thermal tank to greenhouse was done simultaneously. As a result of this study showed that COP of heat pump was increased by 15% or more than that of using normal thermal tank because heat pump was able to take 3 ~ 5 degree Celcius lower thermal thank water constantly.

Keywords