Abstract
Since the cooling performance of a $CO_2$ cooling cycle is varied significantly with a variation of refrigerant charge amount and outdoor temperature, the reliability of $CO_2$ system is down. In this study, the performance characteristics of three kinds of $CO_2$ systems were measured and analyzed by varying refrigerant charge amount and outdoor temperature so as to study the characteristics of variation with cycle option. The applied system options are the single-stage compression(1C-1E) system, two-stage compression with 1-EEV(2C-1E) system, and two-stage compression with 2-EEV(2C-2E) system. The performances of two-stage compression with 2-EEV system were less sensitive than those of other systems and the system operated safely and steadily for wide charge amount. The performance of the two-stage compression with 1-EEV(2C-1E) system was the most sensitive to the charge amount, and that of the single-stage compression(1C-1E) system varied a lot with outdoor temperature.