A Novel Noise Reduction Method for Measuring Partial Discharge in High Voltage Electric Machinery

고압 전기설비 부분방전시험을 위한 노이즈 저감방안

  • Published : 2009.07.14

Abstract

Partial discharges(PD) is a important factor to evaluate the insulation state in high voltage electric machinery. However, measuring PD under the circumstances of power plant is occasionally impossible due to the relatively high magnitude of noise which is emanated from the operating machinery. In some case, the instrument measuring PD can not even perform a calibration that initializes tools and enhance the accuracy. This paper presents that we devised a noise reduction method and demonstrated the usefulness in acquiring reliable PD signals. We attached a series of filter and transformer at the input of power source of the instruments which refrains high noise signals from incoming to the instruments. We experimented the efficiency of noise reduction applying the device into the Dangjin Power Plant and Factory. As a result of testing with the filter and transformer, we can easily calibrate the PD signal compared to the case without the device. Additionally, we can detect the small PD signal which was unperceived with a normal device.

Keywords