Shorted-Turn Diagnosis Test for Generator Rotor Windings using Low Voltage Pulse Signal

저전압 펄스신호를 이용한 발전기 회전자 턴단락 진단

  • Published : 2009.07.14

Abstract

A recurrent surge oscillograph(RSO) test was performed at the Taean thermal power plant on #5 turbine generator. The test was conducted using a rotor reflectometer and digital oscilloscope. A DC voltage step is applied to each end of the rotor winding in turn. Each reflected wave, at the input end of the winding, is monitored and the two waveforms are superimposed automatically and monitored on a single channel oscilloscope. As the half windings in a rotor are identical, the two waveforms monitored at each end of the rotor will also be identical for a healthy winding. A winding with a fault will cause different voltages to be monitored at the two ends.