Long-term thermal performance of evacuated tubular solar collector for demonstration system

태양열 실증시스템의 진공관형 태양열 집열기 장기 열성능

  • 이호 (전주대학교 대학원 건축공학과) ;
  • 주홍진 (한국에너지기술연구원) ;
  • 윤응상 (한국에너지기술연구원) ;
  • 김상진 (전주대학교 건축공학과) ;
  • 곽희열 (한국에너지기술연구원)
  • Published : 2008.04.12

Abstract

This paper presents demonstration study results derived through field testing of a part load solar energized cooling system for the library of a cultural center building located in Gwangju, Korea. First operating demonstration system was set up in Gwangju in 2005. These system comprises the $200m^2$ evacuated tubular solar collector, a $6m^3$ heat storage tank. In a 2006, daily average of insolation showed about $506W/m^2$, the solar collector efficiency was 44%. In a 2007, daily average of insolation showed about$507W/m^2$, the solar collector efficiency was 42%. As a result, evacuated tubular solar collector kept the high efficiency for two years.