Analysis of CFT Column-RC Flat Plate Interior Connections under Lateral Load

횡하중을 받는 CFT기둥-RC무량판 접합부의 해석연구

  • Published : 2008.11.07

Abstract

Flat plate system has many advantages, story height reduction, a term of works shortening and changeableness of space, etc. However structures become a tendency of higher stories and when we use RC column, the size of column grow larger. For this reason the use of CFT column is increasing more and more. Accordingly, this study carried out the nonlinear finite element analysis. As a result of analysis moment strength of the connection increased but ductility decreased as the top reinforcement ratio in th effective width increased. And moment strength and ductility of the connection decreased as gravity load ratio decreased. In the case that shearhead length is not more than 0.27m, the effectiveness of shearhead length on the moment strength and ductility of the connection were small relatively to other variables. Initial stiffness and moment strength of connection increased as slab thickness increased

플렛 플레이트 구조시스템은 층고절감, 공기단축, 공간의 가변성 등 많은 장점들을 가지고 있다. 하지만 건물이 고층화 되어감에 따라 일반 RC 기둥을 사용할 경우 기둥의 크기가 과도하게 커지는 단점이 있다. 이러한 이유로 CFT 기둥의 사용이 증가하고 있지만 CFT 기둥-RC 무량판 접합부의 이력거동을 명확하게 규명하기 위한 기존 실험 연구는 국내외적으로 매우 부족한 실정이고 실험연구를 통해서는 한계가 있다. 본 연구에서는 비선형 유한요소해석을 실시하여 접합부의 이력거동을 분석하였다. 해석결과 유효폭 내에 배근되는 철근비가 증가하면 접합부의 모멘트 강도는 증가하지만 연성능력을떨어졌고 중력하중비가 증가할 경우 접합부의 모멘트강도와 연성능력이 모두 감소하였다. 전단머리의 길이가 0.27m 이상인 경우에는 길이가 증가할 때 다른 변수에 비해 접합부의 모멘트 강도와 연성능력에 주는 영향이 상대적으로 작았다. 슬래브두께가 증가할수록 초기강성 및 모멘트 강도가 증가하였다.