Seismic Performance Evaluation of Piloti-type low-rise RC apartment buildings using Nonlinear Static Analysis

비선형 정적해석을 이용한 필로티형 저층 RC 집합주택의 내진성능평가

  • 이정재 (고려대학교, 콘크리트구조공학연구실) ;
  • 이한선 (고려대학교, 건축사회환경공학과) ;
  • 김희철 (경희대학교, 건축공학과) ;
  • 이영학 (경희대학교, 건축공학과) ;
  • 이기학 (세종대학교, 건축공학과)
  • Published : 2008.11.07

Abstract

The objective of this study is to evaluate the seismic performance of the low-rise RC apartment buildings having piloties at ground level by using nonlinear static analysis with regards to the maximum considered and design earthquakes in Korea. To do this, the target displacement at roof was estimated according to FEMA356 (or ASCE/SEI-41), and the deformations of the critical members were compared with the failure criteria of Life Safety(LS) and Collapse Prevention(CP) given in FEMA356. The conclusions are as follows: (1) columns satisfy criteria of LS and CP, but (2) the shear wall in the longitudinal direction failed to satisfy those of both LS and CP while those in the transverse direction satisfy that of LS, but failed that of CP.

1층에 필로티를 가지는 저층 RC 집합주택의 표준대상구조물을 선정하여 비선형 정적해석에 의해 우리나라 내진 기준에 정하는 최대 지진과 설계 지진에 대하여 내진성능을 평가하는 것이 본 연구의 목적이다. 이를 위하여 FEMA356 (혹은 ASCE/SEI-41) 보고서에 의해 목표 변위를 산정한 후 이 목표 변위에 대한 주요 부재(기둥, 벽체)의 상태를 검토하였다. 이 결과 (1) 기둥은 생명안전수준(LS)과 붕괴 방지 수준(CP)의 요구 조건을 전부 만족하고 있지만 (2) 벽체의 경우 단변 방향은 LS는 만족하였지만, CP는 만족하지 못하였고, 장변 방향의 경우 LS와 CP 공히 만족하지 못하는 것으로 나타났다.