Analysis of Industrial Battery lifetime Using Instantaneous Discharge Test

순간방전 시험에 의한 산업용 축전지 잔존수명 분석

  • 김종민 (한국전기 안전공사 전기안전연구원) ;
  • 방선배 (한국전기 안전공사 전기안전연구원) ;
  • 송길목 (한국전기 안전공사 전기안전연구원) ;
  • 김선구 (한국전기 안전공사 전기안전연구원)
  • Published : 2008.04.18

Abstract

Battery is one of the emergency power. Battery reliability is a very important to keep up the minimum of building capabilities in case of interruption of electric power. Instantaneous discharge test is carried out for measuring transient voltage change(${\Delta}V$) and internal instantaneous impedance(Z), and then it is compared with discharge test results for the estimating the battery capacity. As a result, it was confirmed that the voltage change(${\Delta}V$) and the instantaneous impedance of the batteries failed in actual discharge test were higher that those of the sound batteries. Such an instantaneous discharge test can be a diagnosis of battery sound.