In this paper two kinds of techniques were compared for localization of PD(partial discharge) in power transformer and more useful method was suggested. Both of them, the time of arrival and the energy content method, were tested in 154kV single phase experimental transformer using UHF signal measurement. The former was using the difference of arrival time of recorded signals from four UHF sensors, the latter was based on the energy content in frequency spectra of signals detected at all sensors.