Comparing and Analysis for Classification of PD Source Generated by Electrical Tree

전기트리시 발생하는 부분방전원 분류기법 비교 분석

  • Published : 2007.06.21

Abstract

Solid insulation exposed to voltage is degraded by electrical tree process. And the degradation of the insulation is accelerated by voltage application. For this experimental, specimen of electrical tree model is made by XLPE (cross-linked polyethylene). And the size of the specimen is $7*5*7\;mm^3$. Distance of needle and plane is 2 mm. Voltages applied for acceleration test are 12 kV to 15 kV. And distribution characteristic of degraded stage is studied too. As a PD detecting and data process, discharge data acquire from PD detecting system (Biddle instrument). The system presents statistical distribution as phase resolved. Moreover the processing time of electrical tree is recorded to know the speed of degradation according to voltage.