A Method for Improving Air Distribution Performance at the Residence Ventilation System

주거 환기 시스템의 공기 분배 성능 개선 방안

  • Published : 2007.11.30

Abstract

In the mechanical ventilation system, it is a fundamental condition to distribute the air equally to the each room. In this study, distribution performance of the air distributor which generally connected to a circular duct was investigated by simulation and experiment. In the first CFD analysis, maximum air flow rate deviation was an 63% in the air distributor model. After numbers of model modification and simulation, maximum flow rate deviation was reduced to 19% in the final simulation model. An air distributor which used in the experiment was produced by using data obtained from the final analysis. When experimental result was compared with analysis result, there was a deviation difference as much as 9%.

Keywords