Cooling Characteristic Analysis of Transformer's Radiator

변압기 냉각 특성 해석

  • 김현재 ((주)효성 중공업 연구소) ;
  • 양시원 ((주)효성 중공업 연구소) ;
  • 김원석 ((주)효성 중공업 연구소) ;
  • 권기영 ((주)효성 중공업 연구소) ;
  • 이민제 ((주) 효성 중공업 PG 전력 PU)
  • Published : 2007.05.30

Abstract

A transformer is a device that changes the current and voltage by electricity induced between coil and core steel, and it is composed of metals and insulating materials. In the core of the transformer, the thermal load is generated by electric loss and the high temperature can make the break of insulating. So we must cool down the temperature of transformer by external radiators. According to cooling fan's usage, there are two cooling types, OA(Oil Natural Air Natural) and FA(Oil Natural Air Forced). For this study, we used Fluent 6.2 and analyzed the cooling characteristic of radiator. we calculated 1-fin of detail modeling that is similar to honeycomb structure and multi-fin(18-fin) calculation for OA and FA types. For the sensitivity study, we have different positions(side, under) of cooling fans for forced convection of FA type. The calculation results were compared with the measurement data which obtained from 135.45/69kV ultra transformer flowrate and temperature test. The aim of the study is to assess the Fluent code prediction on the radiator calculation and to use the data for optimizing transformer radiator design.