Dynamic Performance Analysis of Unified Power Quality Conditioner with Cascaded H-Bridges

다중브리지로 구성된 UPQC(Unified Power Quality Conditioner)의 동적 성능분석

  • Published : 2006.04.20

Abstract

This paper describes experimental analysis of UPQC, which is composed of cascaded H-bridges and single-phase multi-winding transformers. The operational characteristic was analyzed through experimental works with a scaled model, and simulations with PSCAD/EMTDC. The UPQC proposed in this paper can be directly connected to the distribution line without series injection transformers. It has flexibility to expand the operation voltage by increasing the number of H-bridge modules. The analysis results can be utilized to design the actual UPQC system applicable for the actual distribution system.

Keywords