The Shaking Table Test of Isolated Model EDG System

면진된 모형디젤발전기의 지진응답실험

  • 김민규 (한국원자력연구소 종합안전평가부) ;
  • 전영선 (한국원자력연구소 종합안전평가부)
  • Published : 2006.03.17

Abstract

This paper presents tile results of experimental studies of the isolated Model EDG Systems. For the experimental work, the scaled model of EDG system and the isolation systems were developed. The target EDG model is 16PC2-5V400 which was manufactured by the SEMT Pielstick corporation. The Coil Spring and Viscous Damper Systems were selected for the isolation system. The Coil Spring and Viscous Damper systems can reduce not only seismic forces but also the operating vibration. For the input seismic motions, the scenario earthquake and the artificial earthquakes which were developed as NRC design spectrum and Uniform hazard Spectrum(UHS) were selected. As a result, at least 20% of seismic forces were decreased as the isolation system.

Keywords