Shaking Table Test Study on 3-Dimensional Floor Isolation of Main Control Room of Nuclear Power Plant
원전 주제어실 3차원 층면진시스템의 진동대 실험 연구
- Published : 2006.03.17
Abstract
The seismic characteristics with 3-Dimensional Floor Isolation System have been studied using a shaking table system. In this study, we made two kind of floor system (Type I, Type II) and several seismic tests with and without isolation system were conducted to evaluate 3-Dimensional Floor Isolation Effectiveness. Both type have showed large reduction effectiveness in acceleration, response spectra but Type II have showed lower acceleration and lower first mode in response spectra, compared to type I. On the basis of test results and consideration of application, it is found that type II is more suitable for floor model of main control room of Nuclear Power Plant.