Analysis on TVOC Concentrations and Influence Factors of Newly-Built Apartments

신축 아파트의 총휘발성유기화합물 농도와 관련요인 분석

  • 최윤정 (충북대학교 주거환경.소비자학과) ;
  • 강미라 (충북대학교 주거환경.소비자학과) ;
  • 이혜민 (충북대학교 주거환경.소비자학과) ;
  • 안혜정 ((주)이도아트)
  • Published : 2006.05.27

Abstract

The purpose of this study was to identify the influence of living factors on TVOC(Total Volatile Organic Compounds) concentrations for newly-built apartments. The field measurements of TVOC concentrations were made totally 30 times(5 times per one subject house) in six apartment units in which residents recently moved. Those apartments authorized its business approval before May 2004, the Act of Indoor Air auality Management for multi-use facilities. The findings were as follows: The TVOC concentrations of the measured subject apartments ranged from about 1/10 of the recommended standard for multi-use facilities($400{\mu}g/m^3$) to up to 90 times as high as the standard. Since then, the Recommended Standard of Indoor Air Quality Management for newly-built apartment house was announced in December 2005. In accordance with this standard($2390{\mu}g/m^3$) it ranged from about 1/100 to up to 15 times as high as the standard. The subject house whose TVOC concentrations reduced below the recommendation standard in the shortest period had the largest amount of ventilation (all the windows were open for ventilation in the past three months) among ail measured houses. The reason of another house whose TVOC concentrations were much higher than the rest was fronted with new furniture in the room. It's recommended that they should open all the windows for at least three months for ventilation in newly-built houses, and it would be better to avoid remodeling than needs be.