A Study on the Method of Estimating Optimum Supply Water Temperature Considering the Heating Load and the Heat Emission Performance of Radiant Floor Heating Panel

난방부하와 온수온돌의 방열성능을 고려한 적정 공급온수온도 산출방법에 관한 연구

  • Choi, Jeong-Min (Department of Architecture, Graduate School, Seoul National University) ;
  • Lee, Kyu-Nam (Department of Architecture, Graduate School, Seoul National University) ;
  • Ryu, Seong-Ryong (Department of Architecture, Graduate School, Seoul National University) ;
  • Kim, Yong-Yee (Department of Architecture, College of engineering, Kunsan National University) ;
  • Yeo, Myoung-Souk (Department of Architecture, Graduate School, Seoul National University) ;
  • Kim, Kwang-Woo (Department of Architecture, College of engineering, Seoul National University)
  • 최정민 (서울대학교 대학원 건축학과) ;
  • 이규남 (서울대학교 대학원 건축학과) ;
  • 류성룡 (서울대학교 대학원 건축학과) ;
  • 김용이 (군산대학교 건축공학과) ;
  • 여명석 (서울대학교 대학원 건축학과) ;
  • 김광우 (서울대학교 건축학과)
  • Published : 2006.06.21

Abstract

A common approach to achieve better thermal comfort with hydronic radiant floor heating system is supply water temperature control. This is the control method through which supply water temperature is varied with outdoor temperature. In this study, a comprehensive, yet simple calculation method to find optimum supply water temperature is evaluated by combining heat loss from the building and heat emission from the hydronic radiant floor heating system. And then the control performance of suggested calculation method is confirmed through experiment. It is shown that indoor air temperature is stably maintained around the set point.