An Experimental Study on the Effects of a Radiation Shield on the Thermal Load of a Cryochamber
복사 차폐막이 극저온 용기의 부하에 미치는 영향에 관한 실험적 연극
- Published : 2005.11.25
Abstract
Infrared (lR) detectors are widely used for such applications as thermoelstic stress analysis, medical diagnostics and temperature measurement. Infrared detectors commonly need to be refrigerated below 80 K, and thus a cooling system should be equipped together with the detector system. The cooling load, which should be removed by the cooling system to maintain the nominal operating temperature of the detector, critically depends on the insulation efficiency of the cryochamber housing the detector. Cryochamber considers the conduction heat transfer through a cold finger, the gases conduction and radiation heat transfer. The thermal loads of an infrared detector Cryochamber with radiation shield are investigated experimentally in present study. Since the effect of radiation heat transfer on thermal loads is significant, radiation shields is installed in the cold finger part to protect heat input through radiation. It is found that the thermal load can be substantially reduced by increasing the number of radiation shield.